  • 层流手术室净化空调系统的维护清理
    来源:http://www.sdyhrs.com 浏览: 发布日期:2019-05-13
    现代医院层流洁净手术室在初次使用的时侯应当让其连续运行超过过二十四小时,经过空气培养两次达标以后才可以正式投入运行,运行以前还应当对各个科室的工作人员进行学习培训,让每个人熟练了解并掌握现代医院层流洁净手术室应当注意的事项。
    The laminar flow clean operating room of modern hospital should be operated continuously for more than 24 hours when it was first used. It can be put into operation only after two times of air training. Before operation, the staff of each department should be trained to know and master the matters needing attention in the laminar flow clean operating room of modern hospital skillfully.
    当需要进行手术,应当在手术一小时以前运行净化空调系统,并清洁物品表面与地面,当手术以后继续运行半个小时,以确保手术室内的空气质量。净化空调系统需安排人员定期与不定期进行维护,遵循设备的使用说明进行保养与维护,并制定运行手册,有检查和记录,尤其包括空气处理机组、新风机组定期检查,保持清洁;过滤器的更换与清洗等。其中,新风机组粗效滤网宜每2天清洁一次;粗效过滤器宜1月―2月更换一次;中效过滤器宜每周检查,3个月更换一次;亚过滤器宜每年更换;末端过滤器宜每年检查一次,当阻力超过设计初阻力160Pa或已经使用3年以上时宜更换;排风机组中的中效过滤器宜每年更换。与此同时,定期检查回风口过滤网,宜每周清洁一次,每年更换一次,如遇特殊污染,及时更换,并用消毒剂擦拭回风口内表面。
    层流手术室净化效果
    When an operation is needed, the air conditioning system should be operated one hour before the operation, and the surface and ground of the articles should be cleaned. After the operation, the operation should be continued for half an hour to ensure the air quality in the operating room. Clean air conditioning system should be maintained regularly and irregularly by professionals, following the instructions of the equipment, and working out operation manual with inspection and record, especially for air handling units and fresh air units, to keep clean, filter replacement and cleaning, etc. Among them, the crude filter of fresh air unit should be cleaned every two days; the crude filter should be replaced every January to February; the intermediate filter should be checked every week and replaced every three months; the sub-high efficiency filter should be replaced every year; the end high efficiency filter should be checked every year, when the resistance exceeds 160Pa of the initial design resistance or has been used for more than three years; the medium efficiency filter in exhaust fan group should be replaced. Replacement every year. At the same time, regularly check the return air filter, it is advisable to clean once a week and replace it once a year. In case of special pollution, replace it in time and wipe the inner surface of the return air with disinfectant.
    除此之外,严格控制手术室内的湿度与温度,温度应当保持在24摄氏度到26摄氏度,湿度应当保持在相对40%到60%左右
    In addition, the humidity and temperature in the operating room should be strictly controlled. The temperature should be kept between 24 and 26 degrees Celsius, and the humidity should be kept between 40 and 60 percent.
    本文的精彩内容就先到这里了,了解更多关于层流手术室装修的详细情况可关注:http://www.sdyhrs.com
    Here's the highlight of this article. For more details about laminar operation room decoration, please pay attention to: http://www.sdyhrs.com

    上一篇:层流手术室夏季除湿有什么必要性?
    下一篇:微生物实验室装修有什么注意要点?