新闻资讯
  • news
  • 咨询热线:
  • 0531-87568508
  • 18653128690
  • 行业新闻
  • 您现在的位置:首页 > 新闻资讯 > 行业新闻 >
  • 静脉药物配置中心几项设备的设置
    来源:http://www.sdyhrs.com 浏览: 发布日期:2017-09-05
    静脉药物配置中心的位置设置
    Location setting of intravenous drug dispensing center
    要远离各种污染源。周围的地面、路面、植被等不应对配置过程造成污染。洁净区采风口应设在无污染的相对高处。应有防止污染、昆虫和其它动物进入的有效设施。
    Keep away from all sources of pollution. The surrounding area, road surface, vegetation and so on should not cause pollution to the allocation process. Clean areas should be located in relatively high export collection without pollution. Effective facilities for preventing pollution, insects and other animals entering.
    静脉药物配置中心的布局设计
    Layout design of intravenous drug dispensing center
    全区域设计应布局合理,保证顺畅的工作流程,各功能区域间不得互相妨碍。配置中心应具备二级仓库、排药准备区、审方打印区、洗衣洁具区、缓冲更衣区、配置区、成品核对区等工作区域。同时在面积充足的情况下应设有其他辅助工作区域如普通更衣区、普通清洗区、耗材存放区、冷藏区、推车存放区、休息区、会议区等。各工作间应按静脉输液配置程序和空气洁净度级别要求合理布局。不同洁净度等级的洁净区之间的人员和物流出入应有防止交叉污染的措施。
    The design of the whole area should be reasonable and ensure a smooth working flow, and the functional areas should not interfere with each other. Configuration center should have two levels of warehouse, drug preparation area, trial printing area, laundry area, buffer dressing area, configuration area, finished product check area and other work areas. At the same time, in the area of sufficient circumstances, there should be other auxiliary work areas, such as general dressing area, general cleaning area, supplies storage area, cold storage area, trolley storage area, rest area, conference area and so on. Each work shall be properly arranged according to the requirements of the intravenous infusion program and the air cleanliness level. Personnel and logistics between clean areas with different cleanliness levels shall have measures to prevent cross contamination.
    静脉药物配置中心送、排、回风要求
    静脉药物配置中心装修
    Requirements for feeding, discharging and return air of intravenous drug dispensing center
    配置中心内需将抗生素类药物及危害药物的配置和肠道外营养及普通药物的配置分开。需要建立两套独立的送排(回)风系统,或配置抗生素类药物及危害药物的洁净区为独立全排风系统。排风口要远离其它采风口,距离不小于3米,排风静脉药物配置中心设备要求
    The allocation of antibiotics and dangerous drugs is separated from parenteral nutrition and the configuration of common drugs. There is a need to set up two independent air supply and drainage systems, or a clean area with antibiotic drugs and dangerous drugs, which is an independent total air exhaust system. The air outlet shall be far away from other air intakes, with a distance of not less than 3 meters, and equipment requirements for the exhaust air intravenous drug dispensing center
    配置中心内抗生素类药物和危害药物的配置,需要在BSCII级生物安全柜中进行。肠道外营养药物和其它普通药物的配置,需要在百级水平层流净化台中进行。
    Configuration of antibiotic drugs and hazardous drugs in the center needs to be carried out in the BSCII biosafety cabinet. The configuration of parenteral nutrition drugs and other general drugs should be carried out in the 100 grade horizontal laminar flow purification platform.
    本文由 静脉药物配置中心装修整理发布,您是不是对这些内容有所了解了呢?更多的内容请点击:http://www.sdyhrs.com我们会有更多精彩内容等你查看。
    This article is arranged and arranged by the intravenous drug dispensing center. Do you know something about it? Please click on http://www.sdyhrs.com for more content. We will have more wonderful content for you to check.

    上一篇:实验室洁净系统是生物安全实验室必备
    下一篇:食品厂净化车间有哪些标准?