  • 医院手术室装修净化的设计
    来源:http://www.sdyhrs.com 浏览: 发布日期:2017-12-22
      装修后的手术室不仅能很好地满足使用功能的要求,也为医护人员和患者营造了一个良好的医疗环境。整体要求包括 ICU 及手术室的准备区、隔离区和手术区三大区域,根据规模大小,按比例合理分割统筹考虑,包括房间设置、设施摆放、通道划分,医护人员与病员、家属之间的关系,要求有序。
      After the decoration, the operation room can not only meet the requirements of the use of functions well, but also create a good medical environment for medical staff and patients. The overall requirements including ICU and operation room preparation area, the isolation zone and the operation area of three regions, according to the size, according to the proportion of reasonable division of the overall consideration, including room setting, facilities placed, channel division, the relationship between medical staff and patients, their families, the requirement of efficient and orderly.
      医用气体、给水排水、配电,保温柜保冷柜应为嵌入式设计
      Medical gas, water supply and drainage, distribution, insulation cabinet for insulation cabinet should be embedded design
      洁净手术部必须设氧气、压缩空气和负压吸引三种气派和装置。需要时还可设氧化亚氮(一氧化二氮即笑气)、氮气、氩气气派以及废气回收排放装置等。医用气体必须有不少于三日的备用量。洁净手术室医用气体终端必须有一套备用。洁净手术部内的给水系统宜有两路进口,并应同时设有冷热水系统。供给洁净手术部的水质必须符合饮用水标准;刷手用水宜进行除菌处理;热水贮存应有防止滋生细菌措施。洁净手术部内应设直消火栓给水系统及手提式气体灭火器。
      The clean operating department must have oxygen, compressed air and negative pressure to attract three kinds of air and equipment. When necessary can also be provided with Nitrous Oxide (two nitrogen oxide or nitrous oxide), nitrogen, argon and air emissions waste gas recovery device. Medical gases must have a reserve of no less than three days. The medical gas terminal of the clean operation room must have a set of spare. The water supply system in the clean operating department should have two routes and should have a hot and cold water system at the same time. The water quality of the clean operating department must be in accordance with the standard of drinking water; the water removal of the brush hand should be carried out, and the storage of hot water should prevent the breeding of bacteria. The direct fire hydrant water supply system and the portable gas extinguisher should be set up in the clean operating department.
      洁净手术部必须设能自动切换的双路供电电源,从其所在建筑物配电中心专线供给。洁净手术室内用电应与辅助用房用电分开,每个手术室的干线必须单独敷设。洁净手术室内医疗设备及装置的配电总负荷除应满足设计要求外,不宜小于8kVA
      The clean operating department must provide a two way power supply that can automatically switch from the special line of the distribution center of its building. The electricity used in the clean operating room should be separated from the auxiliary room, and the trunk of each operation room must be laid alone. In addition to the design requirements, the total distribution load of the medical equipment and equipment in the clean operating room should not be less than 8kVA